4–20 mA Calculator

Instrument scaling, interactive setpoints & loop checks. Use the ? buttons for guidance.

Opening 4–20 mA Calculator…

4–20 mA CalculatorOpen on desktop ↗
PROCESS I/O 4–20 mA
Instrument range

Transfer curve

Setpoints

Receiver, PLC & display
Formulas & references

Linear: mA = 4 + 16 × (measurement − LRV) ÷ (URV − LRV). Inverse: measurement = LRV + (URV − LRV) × (mA − 4) ÷ 16. Reverse ranges use the same equations. Square-root flow uses flow fraction = √signal fraction. Loop voltage margin = supply − transmitter minimum − design current (A) × total resistance.

NI: current loops · Beckhoff: NAMUR reference bands · ICS Schneider: DP flow extraction